How EKX calculates short circuit

This page describes exactly how EKX models each component and solves a short circuit, so you can check its results against a hand calculation or another study and explain any difference. To run the study and read its results, see Running short-circuit analysis.

Method

EKX solves a bolted three-phase fault at the maximum-current case using the equivalent voltage source method of IEC 60909-0 (International Electrotechnical Commission). The network is solved with complex impedances: resistance and reactance are combined in one network, not reduced separately as in the ANSI (American National Standards Institute) C37 procedure. Each source is a shunt impedance, and the fault bus is driven by one equivalent voltage. Every bus that is included in the study is faulted in turn; see choosing which buses are faulted.

The Standard setting under Diagram Settings > Short Circuit shows IEC 60909, the only method available. Where the standard leaves a choice, EKX uses:

  • on the IEC voltage-factor pre-fault basis, the maximum voltage factor c max = 1.10 at every

voltage level, the value for systems with a 10% voltage tolerance, and the transformer correction factor KT on every two-winding transformer (see Pre-fault voltage);

  • the equivalent frequency method (method C) for the peak current at every bus;
  • a 1 s fault duration for the thermal equivalent current;
  • conductor resistance as listed in the cable catalogue, which is 75 °C for built-in cables, where

IEC 60909 bases maximum currents on 20 °C;

  • every running induction motor, with no small-motor exclusion. Only the arc flash study leaves

out motors below 50 hp.

Pre-fault voltage

Choose the basis under Diagram Settings > Short Circuit > Pre-fault voltage. New projects start at Fixed, 100%. Projects created before the setting existed keep the IEC voltage factor until you change it. The arc flash study has its own pre-fault setting on the Arc Flash tab.

IEC 60909 voltage factor (c max 1.10): every bus starts at 1.10 per unit. The utility impedance is c × Un² / Sk'', transformers carry KT and generators carry KG, as IEC 60909 defines them.

Fixed, % of nominal (80% to 120%): every bus starts at that percent of its nominal voltage. The utility impedance is Un² / Sk'', and no correction factor applies, so a generator uses its own Ra + jX''d. This is the usual basis of North American studies. At 100% it gives the same utility current as the IEC basis at a bus fed only by the utility, and lower currents downstream of transformers and wherever motors or generators contribute.

IEC basis:    Ik'' = c × Un / (√3 × |Zk|)
Fixed basis:  Ik'' = (V% / 100) × Un / (√3 × |Zk|)

Un is the nominal voltage of the faulted bus and Zk is the network impedance seen from that bus. Each run records the basis it used, and the report's methodology section names it.

Sources

Utility

A utility is an impedance behind the bus it connects to. EKX takes the fault level from the input method you chose on the utility's Study tab:

MVA method:            S = entered short-circuit MVA,         X/R as entered
Fault current method:  S = √3 × utility kV × entered kA,      X/R as entered
Per unit method:       S = base MVA / |R1 + jX1|,             R/X = R1 / X1
Z = Un² / S   (times c on the IEC basis)
X = Z / √(1 + (R/X)²),   R = X × R/X

A blank, zero or unreadable fault level stops the study and names the field. A utility with several fault cases is solved once per combination of the cases included in the short-circuit study, and each quantity at each location reports the highest value across them; see fault cases.

Generators

EKX models synchronous generators only. The impedance is Ra + jX''d, with X''d in per unit and Ra in percent on the generator's rated kV and MVA. X''d must be above zero. A blank Ra is zero resistance. On the IEC basis the impedance carries the correction factor:

KG = (Un / UrG) × c max / (1 + X''d × sin φrG)

UrG is the generator's rated voltage and φrG the angle of its rated power factor. On the fixed basis KG is 1. For the peak current only, IEC 60909 replaces the generator resistance with a fictitious value of 0.15 X''d at 1 kV or less, 0.07 X''d above 1 kV and under 100 MVA, and 0.05 X''d at 100 MVA and above. Xd', Xd, time constants and grounding data do not enter the solve.

Induction motors

Every in-service induction motor contributes, at any size, unless one of these applies:

  • its State at fault inception is Stopped;
  • every supply reaches it only through a variable-frequency drive with no bypass;
  • it has no horsepower, power or full-load current entered, so it has no size to model.

A motor left at Running (assumed) contributes, and so does a Coasting motor, at full strength. A motor with no classification is modelled as induction. A motor recorded with another classification, such as Synchronous or DC, stops the study with a message naming it. An in-service motor with a size but a blank or zero Locked Rotor Current or R/X Ratio also stops the study.

EKX sizes the motor from its saved full-load current when one exists, otherwise from its power (electrical input, in kW), otherwise from its horsepower. The locked-rotor current then sets the whole impedance magnitude, and the R/X ratio splits it:

S_M = √3 × V_rM × FLA          (from full-load current)
S_M = kW / pf                  (from power)
S_M = hp × 0.746 / (eff × pf)  (from horsepower, kVA)
|Z_M| = V_rM² / (LRC × S_M)
X_M = |Z_M| / √(1 + (R/X)²),   R_M = R/X × X_M

V_rM is the motor's nameplate voltage, FLA its full-load current, LRC the Locked Rotor Current in per unit of full-load current, R/X the motor's R/X Ratio, and pf and eff the motor's power factor and efficiency. This is the IEC 60909 motor model. At its own nameplate voltage the motor supplies exactly LRC × S_M / (√3 × V_rM), which is LRC × full-load current when the size comes from full-load current. On a 480 V bus with an automatic 460 V nameplate, the motor's impedance is based on 460 V, so at a fixed 100% pre-fault voltage it supplies 480 / 460 ≈ 1.043 times LRC × full-load current.

An ANSI-style hand calculation often sets X = 1 / LRC and adds R on top, which gives a larger impedance and a smaller current. The difference grows with R/X:

Motor R/XX/REKX current over ANSI-style current
0.1010.01.005
0.17 (new motor default)5.91.014
0.303.31.044
0.422.41.085

The short-circuit study applies no ANSI first-cycle or interrupting reactance multipliers. Each motor supplies its full locked-rotor current, where an ANSI first-cycle study raises the reactance of most motors of 1000 hp and below by 1.2, and of motors below 50 hp by 1.67, and so gives them less current. Motors carry no correction factor on either pre-fault basis, so on the IEC basis their contribution is 1.10 times the fixed 100% value.

Branches

Transformers

A two-winding transformer is modelled from its kVA, rated winding voltages and impedance (%Z) on its own rating. The resistance comes from the first of these that is entered:

%R = 100 × load losses (kW) / kVA
%R = %Z / √(1 + (X/R)²)
%R = 1.8 below 500 kVA, 1.5 below 2500 kVA, 1.2 from 2500 kVA

A load-loss resistance at or above %Z stops the study. The size-band value is reduced to 0.3 × %Z when it would reach %Z. On the IEC basis the impedance is multiplied by:

KT = 0.95 × c max / (1 + 0.6 × xT)

where xT is the transformer's per-unit reactance on its own rating. On the fixed basis KT is 1. Both bases use the rated turns ratio: the tap position does not change short-circuit results. Magnetizing current and no-load losses are left out. Vector group and grounding do not enter a three-phase fault; the line-to-ground fault uses them (see Line-to-ground faults).

Cables

A cable's impedance is its catalogue resistance and reactance per kilometre times its length, divided by the number of parallel runs. Built-in cables list resistance at 75 °C, and EKX applies no further temperature adjustment. The raceway decides which values a built-in cable uses; see built-in 600 V and 1 kV impedance. A cable size whose catalogue entry has no resistance or reactance stops the study. Cable capacitance is left out.

Devices and connections

Breakers, fuses, switches, motor control devices and connections without a cable are ideal joints with negligible impedance. A closed device passes the full fault current; current limiting by fuses or breakers is not applied. An open device, open connection or out-of-service component opens the circuit.

What is left out

Both bases leave out static loads, capacitor banks, reactors, cable capacitance and transformer magnetizing current. The fault is bolted, with zero fault impedance. Arc resistance belongs to the arc flash study, which runs its own short-circuit solve with its own pre-fault setting.

Reported quantities

Each faulted bus reports:

QuantityMeaningWhere shown
Ikss (kA)Initial symmetrical RMS (root mean square) current, Ik''Canvas, report
Ip (kA)Peak currentCanvas, report
Ith (kA)Thermal equivalent current for a 1 s faultReport
Skss (MVA)√3 × nominal kV × IkssCanvas, report
Ip  = κ × √2 × Ik''
κ   = 1.02 + 0.98 × e^(−3 × R/X)
R/X = (Rc / Xc) × (fc / f),   fc = 24 Hz at 60 Hz, 20 Hz at 50 Hz
Ith = Ik'' × √(m + n),   n = 1
m   = [e^(4 × f × Tk × ln(κ − 1)) − 1] / [2 × f × Tk × ln(κ − 1)],   Tk = 1 s

Rc / Xc is the network resistance and reactance seen from the fault, calculated at the equivalent frequency fc, and f is the project frequency. Because n = 1, Ith assumes the alternating component does not decay.

A load or motor reports the same quantities for the bus at its terminals; the canvas shows its Ikss. A cable reports the highest current at each end, and a transformer the highest current in each winding, across all faulted buses; the canvas shows a transformer's winding currents, and the report lists both. Protection devices report the current through the device for each fault they can see, under Latest study on the Protection tab.

Line-to-ground faults

Every short-circuit run also solves a bolted single line-to-ground fault at each bus, IEC 60909-0 equation (52), and reports it as Ik LG:

Ik LG = 3 × Ikss × |Z1| / |Z1 + Z2 + Z0|

Z1 and Ikss come from the three-phase solve at the same bus, so both currents use the same pre-fault voltage basis. Z2 equals Z1, except that a generator with a stored X2 uses it in place of Xd''. Z0 is the zero-sequence impedance at the bus:

ComponentZero-sequence model
UtilityFrom its line-to-ground data: per unit Z0, or the 1-ph fault current or 1-ph MVA with the 1-ph X/R. A blank 1-ph X/R uses the three-phase X/R.
TransformerZ0 = Z1, with KT on the IEC basis, and no magnetizing path. A grounded wye opposite a delta grounds the wye side. Two grounded wyes pass zero-sequence current through. A delta or an ungrounded wye passes none.
Neutral resistor3 × Rn in series with the winding, where Rn is the line-to-neutral voltage over the Ground fault limit.
CableIts entered Zero sequence R0 and X0, otherwise 3 × its R and X, divided by the parallel runs.
Generatorj X0 on the machine base, with KG on the IEC basis, plus 3 × its grounding resistance or reactance, when grounded.
Motors, loads, capacitor banksNone.

A bus shows Ungrounded when nothing connects its zero-sequence network to ground. It shows no value, with the reason, when that network depends on a missing input:

  • a utility without line-to-ground data, or with data that would need a negative zero-sequence

resistance or reactance;

  • an impedance-grounded transformer without a Ground fault limit;
  • a grounded generator without X0, or a resistance or reactance grounding without its ohms;
  • a wye-wye transformer with one neutral ungrounded, or a zigzag winding, whose zero-sequence

path depends on core construction EKX does not model.

Only the buses that network reaches are affected. A delta winding separates zero-sequence networks, so a 480 V bus behind a delta-wye transformer is solved even when the utility has no line-to-ground data. With several utility fault cases, each case uses its own line-to-ground values; a bus takes the highest Ik LG across the cases, and has none if any case is missing data it needs.

Rating checks

The report's Equipment Adequacy Assessment compares results with ratings as entered, with no adjustment for the X/R ratio at which equipment was tested:

  • A bus's Ikss against its Sym. short-circuit rating and its Bracing rating, and its Ip

against its Peak rating.

  • A protection device's highest Ikss at its own terminals against its interrupting rating at the

operating voltage. Series-rated combinations are not evaluated.

A check passes with a margin of 10% or more of the rating, warns below 10%, and fails when the current exceeds the rating. On the canvas, a bus's short-circuit values turn amber above 80% of its Sym. rating and red above it.

Limits

  • Three-phase and single line-to-ground faults are calculated. Line-to-line and

double-line-to-ground faults are not available, and the line-to-ground fault has no peak or thermal current.

  • Protection devices are evaluated for the three-phase and the line-to-ground fault. A device's

line-to-ground phase and ground currents are read where its three-phase current is read; a device that the solver merges into one bus is evaluated only when every source and ground return is on its far side from the fault.

  • Only the maximum case is calculated. There is no minimum-current case.
  • There is no breaking current (Ib), interrupting-duty or 30-cycle result, and no asymmetrical

RMS current at contact parting.

  • Generators must be synchronous, and motors must be induction.
  • A bus that no source can reach, even with every device closed, stops the study with its name.

A bus cut off only by an open device or out-of-service component shows No supply.