Sizing warnings and errors
The NEC sizing engine validates component data and displays warnings when sizing rules cannot be applied or results may be non-compliant.
Understanding sizing issues
Errors (blocking):
- Prevent sizing calculation from running
- Must be fixed before sizing completes
- Indicate missing required data or invalid values
- Shown in red with error icon
Warnings (non-blocking):
- Sizing completes but results may need review
- Indicate potential NEC violations or edge cases
- Shown in yellow with warning icon
- Results may require engineering judgment
Common sizing status messages
Some frequently seen sizing messages are status indicators rather than warnings or errors:
The last sizing result is historical evidence for a recommendation. A current selection status comes from Recheck, which reads the installed values and current project or scenario facts without writing them. Manual and locked components remain eligible for that check, and a recommendation difference alone is not a failure.
"Pending sizing suggestions":
- Meaning: The editor has calculated proposed changes that have not been accepted yet
- What to do: Review the green suggestions and accept or dismiss them
"No sizing results available.":
- Meaning: No persisted sizing run has been stored for that component yet
- What to do: Use Re-size system to generate detailed sizing results
"Sizing details are stale.":
- Meaning: The saved sizing details no longer match the current live component values
- What to do: Use Re-size system to refresh the stored sizing explanation
Accepted value changed but details still show old calculation:
- Meaning: Most accepted bus, cable conductor, cable parallel-run, and protection-device rated-current suggestions refresh sizing details after writing the value. Transformer accepted values, or unexpected refresh failures, can still leave details stale.
- What to do: Use Re-size system when you need the detailed card to match the accepted value.
Coordinated sizing group could not be applied:
- Meaning: A linked main/aggregate breaker, protected bus, or protected-conductor group failed validation.
- Cause: One linked member is stale, missing, not in Auto mode, topology-changed, or cannot map to an active cable variant.
- Solution: Refresh sizing suggestions, set required members to Auto if appropriate, select a cable series if needed, then accept the group again.
Common sizing errors
Missing conductor data:
- Error: "Cable variant not specified"
- Cause: Cable component created without selecting cable type
- Solution: Select cable series and variant from dropdown
Invalid current value:
- Error: "Load current must be greater than zero"
- Cause: Load power set to zero or negative
- Solution: Enter valid load power (MW or MVAR)
Missing voltage:
- Error: "Rated voltage required for sizing"
- Cause: Component voltage field empty
- Solution: Enter voltage rating in kV
Incompatible installation type:
- Error: "Installation type not supported for this cable"
- Cause: Selected installation method invalid for cable type
- Solution: Choose compatible installation (underground, cable tray, etc.)
Conductor size below minimum:
- Error: "Conductor cannot be smaller than #14 AWG"
- Cause: Calculated ampacity requires conductor smaller than code minimum
- Solution: Verify load current is realistic; minimum #14 for branch circuits
Required rating exceeds the available catalog:
- Error: "Required rating exceeds the largest available standard rating"
- Cause: The calculated bus, transformer, breaker, fuse, or switch requirement is larger than the active catalog supports
- Solution: Add/select suitable equipment data or reduce the design load. Auto-sizing preserves the current value and does not silently select the largest undersized catalog item.
Feeder voltage mismatch:
- Error: "Downstream load voltage is incompatible with the feeder voltage"
- Cause: A reachable load is connected at a voltage that cannot be supplied directly or through a normal line-to-neutral/split-phase relationship
- Solution: Correct the component voltage or add the required transformer. Auto-sizing blocks the affected feeder, bus, or aggregate protective-device proposal.
Protection constraint conflict:
- Error: "Required OCPD rating exceeds cable ampacity" or a configured maximum
- Cause: The true load requirement cannot be satisfied by the protected conductor or explicit device limit
- Solution: Increase the conductor or allowed device rating, or reduce the load. Auto-sizing preserves the true requirement and blocks the proposal instead of rounding it down.
For motor branches, the short-circuit and ground-fault device is not capped at the NEC 430.22 conductor ampacity; NEC 240.4(G) routes that protection to Article 430. A user-entered maximum remains a hard constraint and blocks an incompatible proposal.
Common sizing warnings
High ambient temperature:
- Warning: "Ambient temperature exceeds NEC table range"
- Cause: Ambient temperature >50°C (122°F)
- Impact: May require custom derating factors
- Solution: Verify temperature is accurate; use custom reference tables if needed
High conductor count:
- Warning: "More than 40 conductors in raceway"
- Cause: Bundling adjustment factor table limit reached
- Impact: 40% derating applied; may need larger conductor
- Solution: Reduce conductors per raceway or use multiple raceways
Next size up applied:
- Warning: "OCPD sized to next standard rating"
- Cause: The conductor ampacity falls between standard ratings and all NEC 240.4(B) conditions are satisfied
- Impact: Slightly oversized protection
- Solution: Normal only when the load does not exceed conductor ampacity, the device is 800 A or less, and no lower explicit user maximum controls. Ordinary rounding that remains within conductor ampacity is a standard NEC 240.6(A) selection, not this exception.
Motor starting current high:
- Warning: "Starting current exceeds OCPD rating"
- Cause: Motor FLC × starting multiplier > OCPD
- Impact: May nuisance trip on start
- Solution: Use higher OCPD multiplier (within NEC limits) or soft start
Voltage drop exceeds recommendation:
- Warning: "Voltage drop >3% (NEC recommendation)"
- Cause: Long cable run or high current
- Impact: May cause equipment performance issues
- Solution: When length, voltage, power factor, and cable R/X data are available, auto-sizing can propose a larger conductor to satisfy the voltage-drop limit. Otherwise, add the missing cable data, increase conductor size manually, or reduce run length.
Parallel conductor required:
- Warning: "Single conductor insufficient, parallel runs required"
- Cause: Load exceeds largest single conductor ampacity
- Impact: Need multiple conductors per phase
- Solution: System automatically calculates parallel runs when auto-parallel is enabled; verify acceptable
Auto-parallel applied:
- Not a warning. Auto-parallel is a successful sizing decision.
- Cause: Auto-parallel sizing determined that multiple parallel runs are needed to keep conductor size at or below the configured threshold.
- Impact: Cable parallel runs have been updated automatically.
- Review: Check the selected configuration in the cable sizing details. Adjust auto-parallel settings in Sizing Defaults if the result is undesirable. See Auto-parallel sizing.
Cable series not selected:
- Warning: "Cable has no series selected. Select a cable series to enable auto-sizing."
- Cause: The cable has no cable series assigned, so auto-sizing cannot apply a cable variant
- Impact: Conductor size is calculated but no cable variant is applied to the cable
- Solution: Select the cable on the canvas and choose a cable series from the dropdown in the edit panel
Motor sizing warnings
FLC not in table:
- Warning: "Motor HP not in NEC table, interpolated value used"
- Cause: Non-standard motor size (e.g., 7.5 HP at 460V)
- Solution: Verify motor nameplate FLA; may need to enter custom value
High OCPD multiplier:
- Warning: "Motor OCPD at maximum NEC multiplier"
- Cause: 2.5× FLC for inverse time breaker or 1.75× for fuse
- Impact: May not protect motor adequately
- Solution: Verify motor starting characteristics; consider soft start
Service factor mismatch:
- Warning: "Motor service factor >1.15"
- Cause: Nameplate service factor allows higher continuous current
- Impact: Sizing based on NEC FLC, not nameplate
- Solution: If using higher service factor, size conductors manually
Cable sizing warnings
Temperature termination limit:
- Warning: "Conductor derated to 75°C termination temperature"
- Cause: Using 90°C conductor on 75°C rated terminal
- Impact: Cannot use full 90°C ampacity
- Solution: Normal per NEC 110.14(C); already applied correctly
Derating below 50%:
- Warning: "Combined derating factors <0.50"
- Cause: High ambient temperature + many conductors
- Impact: Need significantly larger conductor
- Solution: Reduce ambient exposure or bundled conductors; verify necessary
Continuous load factor:
- Warning: "125% continuous load factor applied"
- Cause: Load marked as continuous (operates 3+ hours)
- Impact: Conductor and OCPD sized at 125% of load
- Solution: Normal for continuous loads; verify load actually continuous
OCPD sizing warnings
Exceeds conductor ampacity:
- Error: "OCPD rating exceeds conductor ampacity"
- Cause: Next standard OCPD size larger than conductor ampacity
- Impact: The proposal is blocked unless the NEC 240.4(B) next-size-up conditions are satisfied
- Solution: Increase conductor size or reduce the load/device constraint; auto-sizing does not hide the conflict by selecting a device below the required load current
Fuse class mismatch:
- Warning: "Fuse class may not provide adequate protection"
- Cause: Using Class J fuse where Class RK1 or CC recommended
- Solution: Verify fuse class appropriate for application
Breaker interrupting capacity:
- Warning: "Verify AIC rating adequate for fault current"
- Cause: Sizing doesn't check short-circuit level
- Impact: Breaker may fail to interrupt fault safely
- Solution: Run short-circuit analysis and verify AIC ≥ fault current
Resolving sizing issues
For errors:
- Note the specific error message.
- Identify the component with issue (highlighted in editor).
- Open component properties panel.
- Fill in missing data or correct invalid values.
- Try sizing again.
For warnings:
- Read warning message carefully.
- Determine if issue is acceptable for your application.
- If acceptable: Document reason for deviation in project notes.
- If not acceptable: Adjust component properties or use custom values.
Custom overrides
When warnings are acceptable:
- Engineering judgment applied
- Specific application knowledge
- Equipment manufacturer requirements
- Local code amendments
Documenting overrides:
- Note warning in project documentation.
- Explain reason for accepting.
- Get PE review and stamp.
- Include in calculation report.
When not to override:
- Code violation (errors, not warnings)
- Safety concern
- Without engineering review
- Customer requirements prohibit
NEC rule violations
Code violation indicators:
- Shown as errors, not warnings
- Prevent sizing completion
- Must be addressed
Common violations:
- Conductor below minimum size (#14 for branch circuit)
- OCPD exceeds the applicable device-specific motor limit
- Voltage rating mismatch
- Termination temperature exceeded
Resolution:
- Cannot override code violations
- Must fix component data or system configuration
- Contact support if you believe rule misapplied
Sizing result validation
After sizing completes:
- Review sizing results panel
- Check for any warnings
- Verify sizes are reasonable
- Compare to hand calculations if critical
Red flags requiring review:
- Conductor much larger than expected
- OCPD very high relative to load
- Excessive voltage drop
- Parallel conductors when not expected
Custom reference tables
Overriding NEC tables:
- Use organization or user reference tables
- Implement local amendments
- Review the custom-data provenance recorded in sizing evidence
Custom overrides do not provide a CEC or IEC rules implementation and cannot change the project's selected code profile.
Warning changes:
- Custom tables may eliminate warnings
- Or create new warnings
- Verify custom table correctness
See Customizing tables.
When to contact support
Contact support if:
- Error message unclear
- Sizing calculation hangs or crashes
- Results appear incorrect despite valid data
- Code rule seems misapplied
Use the feedback button (bug icon, bottom right of the editor) to send a report. It attaches the current page's diagnostics and, when available, a project export.
Include in the report:
- Expected vs actual results
- NEC article you believe applies
Related topics
- Cable sizing - NEC ampacity calculation details
- OCPD sizing - Protection device sizing rules
- Customizing tables - Override NEC values
- Debug panel - Data inspection