Connection rules
Electrical components must connect according to electrical engineering principles. Understanding valid connection patterns helps you build correct power system models.
Valid connection patterns
These connection patterns represent real electrical systems:
Radial distribution (most common):
Utility Feed → Main Breaker → Transformer → Distribution Bus → Feeder Breakers → LoadsPower flows one direction from source to loads.
With generation:
Generator → Breaker → Bus ← Utility FeedMultiple sources can feed a common bus.
With redundancy:
Utility A ──┐
├─ Transfer Switch → Main Bus → Loads
Utility B ──┘Automatic or manual source transfer.
Multi-level distribution:
Utility → Primary Bus (13.8kV) → Transformer → Secondary Bus (480V) → LoadsVoltage transformation between distribution levels.
Component role classifications
Components have roles that determine valid connections:
Sources (inject power):
- Utility feeds - External grid connection
- Generators - On-site generation
Distribution (route power):
- Buses - Common connection points
- Transformers - Voltage conversion
- Cables - Conductors between points
Protection (interrupt faults):
- Breakers - Resettable overcurrent protection
- Fuses - One-time fault interruption
Loads (consume power):
- Motors - Mechanical conversion
- Generic loads - Any electrical equipment
Source-to-bus connections
Sources must connect to buses (directly or through protection):
Valid:
Utility Feed → Breaker → Main Bus
Generator → Breaker → Emergency BusSources provide the reference voltage (slack bus) for power flow analysis.
Invalid:
Utility Feed → Load (no bus)
Generator → Motor (direct connection)All sources require a bus for proper power distribution and voltage reference.
Bus-to-load connections
Loads connect downstream from buses through protection:
Valid:
Bus → Breaker → Motor
Bus → Breaker → Cable → Load
Bus → Fuse → TransformerProtection devices must exist between bus and load for overcurrent protection.
Invalid:
Bus → Motor (no protection)
Bus → Load (missing breaker/fuse)NEC requires overcurrent protection for all feeders and branch circuits.
Protection device placement
Protection devices sit between sources/buses and loads:
Valid:
Bus → Breaker → Load (protection on load side)
Utility → Breaker → Transformer (protection on line side)Invalid:
Load → Breaker → Bus (reversed - protection on wrong side)
Breaker → Breaker (no intermediate component)Protection must be closer to the source than the component it protects.
Transformer connections
Transformers require connections on both primary and secondary:
Valid:
Primary Bus (13.8kV) → Transformer Primary
Transformer Secondary → Secondary Bus (480V)Transformer impedance isolates primary and secondary voltage systems.
Invalid:
Transformer with only primary connected (no secondary load)
Transformer with only secondary connected (no primary source)Both windings must connect for power transfer and analysis.
Cable connections
Cables conduct power between any two compatible components:
Valid:
Bus → Cable → Load
Breaker → Cable → Motor
Transformer → Cable → BusCables have resistance and reactance that cause voltage drop.
Invalid:
Cable → Cable (series cables should be single cable with combined length)Multiple cables in series should be represented as one cable with total impedance.
Voltage compatibility
Components at different voltage levels require transformers:
Valid:
13.8kV Bus → Transformer (13.8kV/480V) → 480V BusTransformer voltage ratings must match connected buses.
Invalid:
13.8kV Bus → 480V Load (no transformer)
480V Breaker on 13.8kV Bus (voltage mismatch)All components on a bus must have compatible voltage ratings.
Multiple connections
Some components allow multiple connections per handle:
Buses:
- Unlimited connections on top and bottom
- Each connected component gets its own dynamic handle
- See Buses
Most components:
- One connection per handle maximum
- Breakers, fuses, transformers, loads, motors all single-connection
Cables:
- Exactly two connections (one per end)
- Cannot branch - use bus for branching
Power flow direction
Connections should follow typical power flow:
Top to bottom (conventional):
Utility (top)
↓
Transformer
↓
Bus
↙ ↓ ↘
Load Load Load (bottom)This matches industry standard SLD layout conventions.
Bottom to top (generation):
Generator (bottom)
↑
Breaker
↑
BusGenerators inject power upward into the system.
Prohibited connections
The system prevents these invalid electrical connections:
Load to load:
Motor → Load (two sinks, no source)No power source to energize the loads.
Source to source:
Utility Feed → Generator (no bus)Sources require a bus connection point.
Circular references:
Bus A → Transformer → Bus B → Cable → Bus ACreates unsolvable electrical loops in most cases.
Reverse protection:
Load → Breaker → Bus (protection on wrong side)Protection must be upstream of protected equipment.
Grounding and neutral
Current version focuses on phase connections:
- Three-phase connections shown as single line
- Neutral and grounding connections not explicitly shown
- Ground fault analysis requires ground impedance modeling (future feature)
Assume proper grounding per NEC Article 250 for all installations.
Orphaned components
Components must connect to a source-fed network:
Valid network:
- At least one utility feed or generator
- All components trace back to a source
- Complete electrical path from source to loads
Orphaned (invalid):
- Components with no connections
- Components isolated from sources
- Sub-networks without sources
Run validation warnings to identify orphaned components.
Connection validation workflow
Before analysis:
- Verify at least one source exists
- Check all components connect to source-fed network
- Validate voltage compatibility across connections
- Confirm protection devices protect downstream equipment
- Ensure transformers connect both primary and secondary
Validation warnings identify connection violations before calculations.
Related topics
- Understanding components - Component categories and roles
- Connections - Creating and managing connections
- Validation warnings - Connection validation system