How EKX calculates arc flash

This page explains the calculation behind an arc flash study: which model EKX uses, where each input comes from, how the clearing time is found, and which choices can make EKX differ from a hand calculation or another tool. To set up and run a study, see Running an arc flash study.

The model

EKX calculates arcing current, incident energy and the arc flash boundary with the IEEE 1584-2018 model for three-phase alternating-current systems. The equations come from an unmodified open-source implementation of the standard that is checked against the standard's Annex D worked examples and against cases from the IEEE 1584 spreadsheet calculator. EKX does not adjust the equations.

The model covers an open-circuit voltage (Voc) from 208 V to 15 kV. EKX checks every range the standard states before it calculates, and a bus outside any of them gets no result and a reason naming the limit. It never extrapolates. A bus outside the voltage range is reported as outside IEEE 1584 straight away, without asking for an electrode configuration or other geometry that could not change the outcome.

Limit208 V to 600 VAbove 600 V to 15 kV
Bolted fault current0.5 kA to 106 kA0.2 kA to 65 kA
Electrode gap6.35 mm to 76.2 mm19.05 mm to 254 mm
Working distance305 mm or more305 mm or more
Enclosure widthAt least four times the gapAt least four times the gap

The current limit applies to the bolted fault current at the bus, not to the arcing current. Above 600 V the model calculates at 600 V, 2.7 kV and 14.3 kV and interpolates to Voc, as the standard does.

Electrode configurations

EKX supports all five configurations in the standard: VCB (vertical conductors in a metal box), VCBB (vertical conductors ending in an insulating barrier inside a box), HCB (horizontal conductors in a box), VOA (vertical conductors in open air) and HOA (horizontal conductors in open air).

Enclosure size correction

For the three enclosed configurations, the enclosure height, width and depth set the standard's enclosure size correction factor. An enclosure below 600 V whose height and width are both under 508 mm and whose depth is 203.2 mm or less is treated as shallow; every other enclosure is typical. The equivalent enclosure size follows the standard's rules, including its 508 mm minimum for a typical enclosure and its 1244.6 mm cap. A correction factor outside 0 to 3 is outside the model. Open-air configurations take no correction (factor 1.0), but EKX still needs all three dimensions, and the width must still be at least four gaps.

Geometry and defaults

Each bus takes its geometry from what you enter on its Study tab. A blank field takes the value of the bus's equipment class. The results record which values came from the class.

Equipment classConfigurationGap (mm)Working distance (mm)Enclosure H × W × D (mm)Main isolated
PanelboardVCB25457508 × 508 × 254No
SwitchboardVCB32457508 × 508 × 254No
Motor Control Center (MCC)VCB25457660 × 660 × 254No
Low Voltage SwitchgearVCB32610914 × 914 × 914Yes
Medium Voltage Switchgear (5kV Class)VCB104914914 × 914 × 914Yes
Medium Voltage Switchgear (15kV Class)VCB152914914 × 914 × 914Yes
Cable Junction BoxVCB13457305 × 305 × 203Yes
Open AirVOA152914-Yes
Other EnclosureVCB32457508 × 508 × 254No

A bus with no equipment class uses an assumed VCB geometry chosen by Voc, so a newly drawn bus can be studied without first picking a class. EKX does not assign a class; results, reports and labels say the geometry was assumed.

VocGap (mm)Working distance (mm)Enclosure H × W × D (mm)
0.208 kV to 0.600 kV32457508 × 508 × 254
Above 0.600 kV to 1 kV32610914 × 914 × 914
2.4 kV to 5 kV104914914 × 914 × 914
Above 5 kV to 15 kV152914914 × 914 × 914

There is no assumed geometry between 1 kV and 2.4 kV. A bus there with no class needs its geometry entered. A bus with no class is treated as not isolated.

Arc voltage and pre-fault voltage

The arc flash study has its own pre-fault voltage setting, separate from the short-circuit study's (see Pre-fault voltage). New projects start at a fixed 100% of nominal.

The voltage EKX uses is the bus's nominal voltage in the run's own solved network, with the scenario applied, not the value stored on the bus. The open-circuit voltage in every IEEE 1584 equation then follows the pre-fault setting, so the bolted current and the arc model stand on the same voltage:

Fixed percent P:          Voc = V_nominal × P / 100
IEC 60909 voltage factor: Voc = V_nominal

With a fixed percent, the fault solve starts every bus at that percent, takes the utility impedance as Un² / Sk'' and applies no transformer or generator correction factors. With the IEC 60909 voltage factor, the solve uses the IEC factor but the arc model stays at nominal voltage.

Because the range checks read Voc, a 208 V bus below 100% falls outside the model, and a 600 V bus above 100% is calculated with the above-600 V equations. Results, reports and labels show the nominal voltage; each result records the Voc it used.

Full and reduced arcing current

IEEE 1584-2018 evaluates every location at two arcing currents. EKX calculates both:

I_arc_min = I_arc × (1 - 0.5 × VarCf)

VarCf is the standard's arcing current variation correction factor for the electrode configuration and Voc. Each case gets its own clearing time at its own arcing current, and its own incident energy. The case with the higher incident energy governs the reported energy, the arcing current shown on the results row and the duration. A lower current can fall into a slower part of a protection curve, so the reduced case often governs. The reported boundary is the larger of the two cases' boundaries, which can come from the other case.

Bolted fault current

An arc flash run performs its own short-circuit calculation; it does not read the latest short-circuit study. The bolted current is the three-phase initial symmetrical current at the bus from that solve, at the arc flash pre-fault voltage. At a bus a running motor of 50 hp or more can feed, the reported bolted current is the first-cycle stage's, with each motor's duty multiplier applied (see Motors).

This solve differs from an ordinary short-circuit study in three ways: it uses the arc flash pre-fault setting, it leaves out motors under 50 hp, and at a bus a motor feeds it applies the first-cycle multiplier, 1.2 on a medium motor's impedance (see Motors). An arc flash bolted current can therefore be lower than the short-circuit result on the drawing. These rows stay with the arc flash run and never replace the short-circuit results. Where the bolted current with every motor included differs by more than 0.5%, the results window shows it beneath as All motors and the report adds a column.

Clearing device

EKX follows the source-to-fault path from the run's own solve, using the switching state of the scenario, and credits the nearest upstream device that can interrupt the arc. A switch with no fuse, trip unit or relay that trips it cannot interrupt, so the search passes through it. A CT never interrupts; the search passes through it too.

A bus's main assembly is the run of devices joined to the bus, and to one another, with no cable, transformer or other bus between them. Main device isolation decides which device is credited:

  • Isolated: the nearest creditable device is credited, including the bus's own main.
  • Not isolated: every device in the main assembly is treated as inside the enclosure, with its line

side exposed, so the nearest creditable device beyond the assembly is credited.

The bus setting wins; a blank setting takes the equipment class default in the table above. The basis is the IEEE 1584 guidance that an arc on the line side of a main in the same enclosure is cleared by the upstream device. Compartmented switchgear is the accepted exception, which is why the switchgear classes default to isolated. A bus whose only creditable devices sit in an unisolated main assembly gets no result; the reason names the connection where a device would be credited, usually the transformer primary.

The credited device must disconnect every sustained supply to the fault. If sources reach the bus through different nearest devices, or a supply path survives the device opening, the bus gets no result rather than a chosen or averaged time. A bus a running motor of 50 hp or more can feed is the exception: its event sequence credits a device on each supply path (see Protection while the motor current falls).

A device sees the arcing current, not the bolted current. EKX takes the current the solve assigns to the device and scales it by each case's ratio:

I_device_arcing = I_device_bolted × (I_arc / I_bf)

This keeps currents on the correct winding when the device is on a transformer primary.

Clearing time

The clearing time is read from the credited device's characteristics at its arcing current, for each case. Every function on the device that applies to phase current and can give a clearing time is evaluated, and the fastest one governs. Ground and neutral functions are not credited, because a three-phase arc gives no evidence of ground current. A device whose functions are all below pickup has no clearing time; not tripping is not treated as a very long time.

Each curve is read on its conservative edge. A setting nobody has chosen starts at the slowest published setting. A trip unit or thermal-magnetic part takes its highest pickups and longest delays, and a breaker with published profiles takes its slowest profile. A relay starts 51P at the breaker's rated current (its highest pickup when no rating is recorded), on its first listed curve at that curve's highest time dial, with 50P off. EKX never assumes a characteristic from a device's rating alone, so a device with no catalogue model gives no clearing time.

Fuses

A fuse clears on its published total-clear curve, never its minimum-melt curve. When the arcing current is above the curve's last point, EKX uses the time at that point, because a fuse clears no slower at a higher current; the curve is not extended, and the result is flagged as held at the fuse curve's fastest published time. Below the curve's first point there is no time. Where a curve reaches the arcing current more than once through a vertical step, the slowest time there is used.

A fuse whose maker publishes only an average-melt curve clears at:

t_clear = max(0.010 s, t_average × 1.10 + 0.004 s)

Above that curve's highest current, the clearing time is 0.010 s.

Breakers and trip units

Imported low-voltage breaker and trip-unit curves are saved with their upper band edge as total clearing time, so no separate mechanism time is added. A band whose curve ends below the arcing current is held at its last point and flagged, as for fuses.

An arcing current at or up to 0.5% above a vertical step in a band, such as the top of a magnetic pickup band, reads at the top of the step. This only ever lengthens a time. For a fixed electronic trip unit, each long-time or short-time band ends at the next function's upper pickup, so a slower function never clears faster than the function that took over.

Relays

A relay is drawn on the diagram: it measures the current through the CT its dashed CT line comes from, and it opens each device chosen under Trips in its edit panel. A relay curve gives operating time only. A tripped device's clearing time from that relay is the relay's operating time at the CT's current plus the tripped device's total clearing time, or its opening time plus arcing time, from that device's breaker settings, converted from cycles at the project frequency. The CT can be anywhere on the drawing, including across a transformer from the device it trips: the relay is timed on the current the solve finds through the CT for the same fault.

A tripped device clears at the earliest of its own trip unit or fuse and every relay that trips it. A relay whose tripped breaker has no timing entered gives no clearing time; EKX does not assume a typical breaker time. A relay with no CT line, or with nothing to trip, takes no part in any study. If the solve cannot find a current through a relay's CT for a fault, that relay is not used for that fault, and the bus is left without a result only when nothing else clears it.

Duration

The arc duration for each case is the device clearing time, unless you accept a duration on the bus. An accepted duration needs a basis, a source and a reason it applies, plus worker movement for an exposure assumption, and records who accepted it and when.

  • Documented device time or utility documented time replaces the device time for both cases.
  • Exposure assumption is the longest a worker stays. Each case uses the lesser of its device time

and the accepted time, so a case the device clears sooner keeps its device time.

Any accepted basis gives a duration to a bus with no upstream device, and to a case whose device has no clearing time. Without an accepted duration, either leaves the bus without a result. EKX never falls back to two seconds on its own.

The two-second cap is off by default. When you turn it on, it applies only to buses with a complete accepted exposure assumption. There it applies last, to whichever time each case ended with, including a device time the exposure assumption left in place. It never shortens a documented device or utility time, or any time at a bus without an exposure assumption. Every duration that did not come from the device is flagged on results, reports and labels.

Incident energy and boundary

With a duration for each case, the model returns incident energy at the working distance and the arc flash boundary, the distance at which incident energy falls to 1.2 cal/cm². Displayed boundaries are rounded up: to the next inch or millimetre on labels and the diagram, and to the next 0.01 m in the results window.

Above 600 V, the reduced case's energy uses the reduced arcing current at each of the three intermediate voltages, as IEEE 1584-2018 and its Annex D.1 worked example do. The IEEE spreadsheet calculator version 2.6.6 keeps the full intermediate currents in that term, and tools that follow it report a higher reduced-case energy. On one 630 V example the two methods gave 3.62 and 5.06 cal/cm². At or below 600 V both methods agree.

Utility fault cases and scenarios

When a utility has several fault cases included in arc flash, EKX solves every combination of the included cases across utilities, up to 16. At each bus the solve with the highest incident energy governs, and every value on the row comes from it. The boundary is the largest across all solves and both arcing currents. If any included case has no result at a bus, the bus has no result, because the missing case could be the worst.

The worst case across scenarios applies the same rule over the scenarios: the highest energy governs, a scenario in which the bus has no supply is skipped, and any other scenario without a result leaves the bus without one. See Running an arc flash study for the procedure.

Motors

A running induction motor keeps feeding an arc after the fault starts, and its current falls as the motor slows. EKX follows that fall in stages, re-solving the network at each stage, and lets the protection operate on the current of each stage.

Which motors contribute

A motor contributes when it is in service, running (assumed or verified), an induction motor (a blank motor type is taken as induction), rated 50 hp or more, and connected directly or through a drive with Bypass ticked. The size comes from the horsepower you enter; without it, an entered power converts at 0.7457 kW per hp, rounded to 0.01 hp. Exactly 50 hp counts.

With only full-load current entered, EKX takes the largest rating that current allows, √3 × V × I ÷ 745.7 W at the motor's nameplate voltage, since power factor times efficiency is never more than 1. If that is under 50 hp, the motor is left out like any small motor. If it is 50 hp or more, the current alone can't settle the size: enter the motor's horsepower or kW. For example, 8.8 A at 575 V allows at most 11.75 hp and is left out; 46.8 A at 460 V allows 50.00 hp and needs a horsepower or kW.

Motors under 50 hp are left out of the arc flash solve entirely. If the small motors that can reach a bus supply more than 10% of its arc flash bolted current, the results window and report warn; the numbers do not change. A motor that is out of service, recorded as stopped, or reached by every source only through a variable-frequency drive (VFD) without a bypass supplies nothing.

A motor EKX cannot model makes the buses it can reach unavailable, naming the motor: a coasting motor, a synchronous, DC or other non-induction motor, or a motor with no resolved rating (no horsepower, power or full-load current, or a full-load current that could be 50 hp or more). A bus fed only from the output of a VFD has no result.

Duty class and multipliers

Each contributing motor takes a duty class from its rating and speed, and the class sets a multiplier on the motor's impedance at each stage, following the ANSI/IEEE C37.010 duty stages as given in IEEE 3002.3-2018.

ClassRatingFirst cycleInterruptingFrom 30 cycles
LargeAbove 1000 hp at 1800 rpm or less, or above 250 hp at 3600 rpm (two-pole)1.01.5Removed
Medium50 hp to 1000 hp, not large1.23.0Removed

Speed matters only above 250 hp. If the pole count is blank there, the motor is taken as large, which leaves more motor current in the arc.

Stages and times

StageCycles after the fault startsAt 60 Hz
First cycle0 to 20 s to 0.0333 s
Interrupting2 to 300.0333 s to 0.5 s
Motors removed30 and later0.5 s and later

Cycles convert to seconds at the project frequency. Each stage is a step: the current is constant within it, so the energy of a stage is exactly proportional to its length.

The ANSI duty stages give a momentary value up to the first cycle, an interrupting value from two cycles, and no induction motor current from 30 cycles. They give no value between the first and second cycle, so they do not say when an arc flash calculation should switch from the first-cycle value to the interrupting value. EKX holds the first-cycle value until two cycles. That uses only values the standards state, extends the stated first-cycle value rather than inventing one between them, and keeps the larger motor current in the gap. Holding the first-cycle value longer, for example to four cycles, gives slightly more energy: about 1% on one test circuit.

How the motor impedance is modelled

A motor's locked-rotor current sets the size of its whole impedance:

|Z_motor| = (1 / I_LR_pu) × V_rated² / S_rated

S_rated is the motor's rated apparent power. The motor's R/X ratio splits that impedance into resistance and reactance. A stage multiplier scales the whole impedance, and the network is solved again; EKX never scales a solved current, because removing motor current raises the voltage the remaining motors see. A method that takes only the reactance from the locked-rotor current and then adds the resistance gives a motor current lower than EKX's by a factor of sqrt(1 + (R/X)²), about 1.1% at an X/R of 6.7.

At a fixed pre-fault voltage of 100%, the motor current is the ANSI duty value. With the IEC 60909 voltage factor it is higher by that factor, about 10% at low voltage, which raises the energy.

Energy across stages

EKX walks the arc as a series of intervals. A new interval starts at each stage change, each device trip or opening, and each accepted time. For each interval EKX solves the network with every motor at its stage and every opened device removed, takes the IEEE 1584 arcing current from that bolted current, and calculates the incident energy for that interval's length. The total energy is the sum of the intervals. The boundary is worked from the summed energy, not taken as the largest interval's; above 600 V the energies are summed at each of the standard's intermediate voltages before interpolation.

The full and reduced arcing currents are walked as two separate sequences, because they can clear in a different order. The case with the higher total energy governs, as at any other bus. The results window, report and label show the bolted and arcing currents of the first-cycle stage.

Protection while the motor current falls

In each interval the arcing current is shared among the devices in proportion to their solved currents. Each credited device then advances by its own rule:

  • A relay inverse-time element adds up its progress: each interval contributes its length divided

by the relay's operating time at that interval's current, and the relay operates when the total reaches one. Falling below pickup starts the total again from zero.

  • A relay instantaneous element, or a breaker magnetic element with a published delay, trips only

if the current stays at or above pickup for the whole delay.

  • Fuses and breaker or trip-unit bands have no memory of an earlier current: the device's own current

must hold for its time at that current. A motor stage or another device's opening that leaves its current as it was does not start the time again. When its own current changes, it does. A device that opens this way is recorded as a bounding model, because a restart can only lengthen the duration. Where a closed tie or a parallel route shares the supply, the device left closed carries more current once another opens, and restarts at that higher current. Such a bus is followed this way with or without a motor; without one there are no stage changes.

  • Once only motors feed the arc, a current below the IEEE 1584 range is counted at the lowest current

the standard covers, 0.5 kA up to 600 V and 0.2 kA above, until the motors drop out at 30 cycles. No device operates on it. This can only overstate the energy, and the sequence says so.

  • A relay is timed on the current through its CT in each interval. Once it operates, every

credited device it trips opens after that device's own mechanism time, whatever the current does next; a tripped device with no mechanism time entered does not open.

A relay without directional control is timed on the size of its current, so a motor feeding the arc back through its feeder breaker is timed the same way as current from the supply. A relay with directional control judges direction at its CT.

The arc ends when every source is cut off: a device opening on each path, or the motors removed at 30 cycles. A motor feeder with no protection device is ended at 30 cycles by the method, and the result says the clearing time is motor contribution to 30 cycles. Cleared by names every device that opened, in order, then motor decay where the 30-cycle stage ended the arc. In the results window, Sequence under the bus's Cleared by lists each case's steps with their times, and the report gives the same steps in a table.

An accepted documented device or utility time sets when the supply's credited device opens, or every one of them where the supply reaches the bus by parallel paths; motor feeders and the stages still decide the motor tail. An accepted exposure assumption limits the whole arc, and the two-second cap applies after it, as at any other bus.

Some cases stop the calculation, and the bus gets no energy, boundary or label, with how far the arc was followed: a relay inverse-time element whose current rises from one interval to the next before its relay has tripped, a relay with directional control on carrying current from its load side, a remaining current outside the IEEE 1584 range, a motor-only island that crosses a transformer, more than 64 intervals in one case, or more than 5 s of calculation for one bus.

Generators

A synchronous generator's fault current falls during the arc, so every bus a generator can feed is calculated state by state, as at a bus a motor feeds. The generator steps through three stages, each solved again with the machine at one reactance:

StageReactanceStarts at
SubtransientXd''Fault inception
TransientXd', or Xd'' held when Xd' is blankT''d = T''do × Xd'' / Xd', or 4 cycles when T''do is blank
Steady stateThe sustained fault current, or XdT'd = T'do × Xd' / Xd, or 30 cycles when T'do is blank

Each step falls at its time constant, so the held current carries the same current-time integral as the exponential decay it stands for. A generator with no Xd' entered keeps Xd'' through the transient stage, and the result's duration says so. A sustained fault current of p percent of rated current is modelled as the reactance 100 / p per unit, the one that gives that current for a fault at the generator's terminals.

The steady state comes from, in order:

  1. The generator's Sustained fault current on its Study tab, for example 300 for a PMG or

AREP set. Its Hold time, for example 10, is how long the regulator holds it; after that the set shuts down and stops supplying the arc, even where no protection device is between the generator and the bus. A blank hold time holds it until a device clears.

  1. Generators without a sustained current in Arc Flash settings, which assumes one percent

for every generator with none entered. It is off by default, and each result that uses it says so.

  1. Neither: EKX calculates the arc twice, once decaying to Xd with no excitation support and once

holding 300 % of rated current, and reports whichever gives more incident energy. The duration says which one it reports.

Neither end is safe on its own. A higher current gives more energy through a device that clears either way, while a lower one can fall below a breaker's pickup and make the arc last longer. When only one of the two calculations reaches a result, for example because nothing clears the current Xd gives, the bus gets no result and the reason names the generator. Enter its sustained fault current, or assume one in settings, and run the study again. For a shunt-excited set with no support, enter 100 / Xd percent, such as 38 for Xd 2.6.

The short-circuit results and every equipment duty keep Xd''. Only the arc flash duration and energy use the decay.

Labels

A label's header reads DANGER at or above the project's danger threshold (8 cal/cm² by default) and WARNING below it. EKX does not assign a PPE (personal protective equipment) category; the label refers the reader to the selected standard for PPE. The limited and restricted approach boundaries and the glove class are looked up by nominal voltage in NFPA 70E 2024 Tables 130.4(E)(a) and 130.7(C)(7)(a), or CSA Z462:21 Tables 1A and 4A. A bus without a result gets no label.

What the calculation does not cover

  • Single-phase, direct-current and load-terminal arcs, and voltages above 15 kV.
  • Buses fed only from the output of a VFD.
  • Synchronous, DC and coasting motors, which make the buses they can reach unavailable.
  • A generator with no sustained fault current whose decay to Xd decides the clearing device, or one

with neither a sustained fault current nor Xd when the arc lasts into its steady state; see Generators.

  • Any bus outside the IEEE 1584-2018 ranges above.

In each case the bus is listed without a result, with the reason, rather than given an approximate number.