Loads and motors

Loads and motors consume electrical power. Loads represent general equipment while motors are specifically rotating machinery with special electrical characteristics.

Generic loads

Generic loads represent any electrical equipment that consumes power:

  • Lighting systems
  • Receptacle circuits
  • HVAC equipment (non-motor)
  • Electronic equipment
  • Resistive heating
  • Static loads

Use the generic load component when equipment is not a motor or when modeling aggregate loads.

> Note: Capacitor banks are their own component, not a load type. See Capacitor banks.

Motors

Motors convert electrical power to mechanical rotation:

  • Pumps
  • Fans
  • Compressors
  • Conveyors
  • Machine tools
  • Any rotating equipment

Motors have special electrical characteristics (starting current, power factor, efficiency) that affect sizing and protection.

Creating loads and motors

  1. Drag Load or Motor from component toolbar.
  2. Drop on canvas.
  3. Connect top handle to upstream bus or protection device.
  4. Configure power consumption in edit panel.

Load types and characteristics

Load type affects how load behaves during voltage changes:

Constant power:

  • Power remains constant regardless of voltage
  • Most electronic equipment
  • Default assumption for general loads

Constant impedance:

  • Power varies with voltage squared (P ∝ V²)
  • Resistive heating elements
  • Incandescent lighting

Constant current:

  • Power varies linearly with voltage (P ∝ V)
  • Some motor loads

Select constant power unless you have specific information about load characteristics.

Load factor

The load_factor field scales the load's power consumption for analysis purposes. A load factor of 0.8 means the load operates at 80% of its rated power during power flow analysis. This is useful for modeling typical operating conditions where equipment does not run at full nameplate rating.

Set load factor to 1.0 for worst-case (full load) analysis, or a lower value to represent typical demand conditions.

Active power and reactive power

Loads consume both real power (MW or kW) and reactive power (MVAR or kVAR):

Active power (real power):

  • Performs useful work
  • Measured in megawatts (MW) or kilowatts (kW)
  • Converted to heat, light, or mechanical energy
  • Specify based on nameplate or load calculation

Reactive power:

  • Magnetizing current for inductive loads
  • Measured in MVAR or kVAR
  • Required for motors and transformers
  • Calculate from active power and power factor:
  Q = P × tan(arccos(PF))

Alternatively, specify power factor and system calculates reactive power automatically.

Rated current field

Rated Current is a design input current (connected/nameplate-style), not solved running current from power flow.

  • If you edit Rated Current, the form recalculates active/reactive power from voltage and power factor.
  • If you edit active power, voltage, or power factor, the form recalculates Rated Current.
  • Cable auto-sizing uses ratedCurrent when it is provided.
  • Standard OCPD auto-sizing currently derives current from active power, voltage, and power factor.

Power factor configuration

Power factor (PF) relates real power to apparent power:

Power Factor = Active Power / Apparent Power
PF = kW / kVA

Typical power factors:

Load TypeTypical PF
Resistive heating1.0 (unity)
Lighting (LED)0.9-0.95
Lighting (fluorescent)0.85-0.90
Motors (induction)0.80-0.88
Welders0.60-0.70
Electronic equipment0.95-1.0

Lagging power factor (0.8-0.95) is most common for industrial loads with motors and transformers.

Motor-specific settings

Nameplate voltage and supply voltage:

  • Nameplate voltage (V) starts in Automatic, showing the assumed motor rating

for the connected supply: for example, 460 V on a 480 V supply or 575 V on a 600 V supply.

  • Automatic follows later supply changes. Select a listed rating or Custom and enter volts

to keep a fixed rating. Choose Automatic to resume following the supply.

  • Supply voltage comes from the connected circuit. A disconnected motor shows an unresolved

supply and has no automatic rating in the panel.

  • Check the actual nameplate for drive-fed, dual-rated, or unusual motors. The 208 V supply

default is 200 V; choose 208 V explicitly if that is the motor rating. Unlisted supplies keep their voltage rather than receiving an estimated reduction.

  • Existing motors with no fixed rating use Automatic. This can change their study results;

saved entered and unconfirmed currents remain unchanged.

  • NEC Table FLC displays the horsepower/voltage lookup separately from entered current.

The motor panel does not display an NEC table value for a CEC project.

  • Enter Nameplate FLA, or confirm a Saved current against the actual motor nameplate.

Editing horsepower, power, or voltage preserves confirmed nameplate current. Table lookup current is not a measured or entered nameplate value.

Horsepower:

  • Mechanical output power at the shaft
  • Nameplate rating
  • Example: 50 HP, 75 HP, 100 HP
  • SI equivalent: 1 HP ≈ 0.746 kW

Power (kW):

  • Electrical input power, the same quantity a meter would read
  • Studies convert it to shaft output using the efficiency below, so the two fields do not have to

agree numerically for the same motor

  • Stored to the nearest 0.1 kW
  • Enter horsepower when you have it; it is the nameplate value, needs no conversion, and is what

an arc flash study uses to decide whether a motor is large enough to count

Full-load current (FLC):

  • Entered value represents motor nameplate current.
  • General branch conductor and OCPD sizing first uses the exact applicable value from NEC Table 430.248 (1-phase) or 430.250 (3-phase).
  • If the table has a dash, the horsepower is nonstandard, or the application needs nameplate current, EKX uses the entered value instead of inventing a nearby table value.
  • The overload recommendation beside Service Factor uses nameplate current, per NEC 430.32.

Typical values on a new motor:

Every study needs a motor's power factor, efficiency, locked-rotor current and R/X, so a new motor starts with typical induction-motor values. Replace them with nameplate or manufacturer data when you have it.

FieldNew motorWhere to change it
Power Factor0.85Equipment tab
Efficiency0.9Equipment tab
Locked Rotor Current6 per unit (6 × full-load current)Study tab
R/X Ratio0.17Study tab

A blank power factor or efficiency stops every study; a blank locked-rotor current or R/X stops short circuit and arc flash. The study message names the motor and the field.

Power factor:

  • Typical range: 0.80-0.88 for induction motors
  • Lower at partial load

Efficiency:

  • Mechanical output / Electrical input
  • Typical range: 0.88-0.95 for modern motors
  • Higher for larger motors
  • Premium efficiency motors: 0.93-0.96

Locked rotor current:

  • Current at the first instant of starting, in per unit of full-load current
  • Typically 5-8× full-load current
  • Sets the motor's contribution to short-circuit and arc flash current

Motor state at fault inception

A motor that is turning when a fault starts feeds that fault for as long as it keeps turning. Whether the motor is in service does not answer that question: a connected motor can be stopped, and a motor with no load can still be spinning.

Studies assume an in-service motor is running unless you say otherwise. The field on the motor's Study tab shows Running (assumed) until you record something, so you can see the assumption before a study uses it.

SettingWhen to use itWhat studies do
Running (assumed)Nobody has checkedThe motor feeds the fault. This is the default and is flagged as an assumption.
Running (verified)You have confirmed it runs at the time of interestThe motor feeds the fault, recorded as verified rather than assumed.
StoppedYou have confirmed it is not turningThe motor supplies no fault current. It still draws its load in power flow.
CoastingIt is turning but already disconnected from its supplyShort circuit keeps it at running strength, which is the conservative choice for equipment duty. Arc flash leaves the location unavailable, because no decay model is approved for a coasting machine.

Clearing the field returns to Running (assumed). Recording a state is an engineering judgment about a moment in time, so it is never set for you.

Poles:

  • 120 × frequency ÷ synchronous rpm; a 1800 rpm motor at 60 Hz has 4 poles
  • Only matters above 250 HP, where speed decides which duty class an arc flash study applies
  • Left empty, an arc flash study takes the class that gives the larger motor contribution

Motor starting methods

Direct-on-line (DOL):

  • Full voltage applied at start
  • Highest starting current (6-8× FLC)
  • Simplest and most common
  • Used for motors <50 HP on stiff systems

Star-delta (wye-delta):

  • Starts in wye, transitions to delta
  • Reduces starting current to ~33% of DOL
  • Common for 50-200 HP motors

Soft starter:

  • Electronic voltage ramping
  • Adjustable starting current
  • Smooth acceleration

Variable frequency drive (VFD):

  • Frequency and voltage control
  • Lowest starting current
  • Speed control capability
  • Highest cost

Starting method affects conductor sizing and protection device selection.

Motor protection and sizing

Motors require special NEC sizing rules:

Conductor sizing:

Branch circuit protection:

  • 2.5× FLC for inverse time breakers
  • 1.75× FLC for time-delay fuses
  • See OCPD sizing

Overload protection:

  • 115-125% of motor FLC
  • Separate from branch circuit protection
  • Protects motor from overheating

Load annotations

After power flow, loads and motors show:

Current:

  • Actual current drawn
  • Compared to rated current for motors

Power:

  • Active power (MW or kW)
  • Reactive power (MVAR or kVAR)

Terminal voltage:

  • Actual voltage at load connection
  • Color-coded if too low (<95%) or too high (>105%)

Low terminal voltage causes motors to overheat and fail to develop rated torque.

Voltage rating

Specify nominal equipment voltage:

Common VoltagesApplication
120VLighting, receptacles
208VSmall equipment, 3-phase lighting
240VResidential/commercial equipment
480VIndustrial motors, large equipment
600VIndustrial, Canadian systems

Equipment can typically operate ±10% of rated voltage, but performance degrades outside ±5%.