Fault types
Short-circuit studies use different fault types depending on the engineering question. Each type produces different fault currents and affects equipment differently.
EKX's current production calculation path supports validated three-phase maximum-current analysis only. The other fault types below are engineering background and planned validation scope, not currently enabled production workflows.
Three-phase fault (3ph)
Most severe fault:
- All three phases short-circuited together
- Highest fault current magnitude
- Balanced fault (symmetrical on all phases)
- Used for equipment rating verification
When to use:
- Breaker interrupting capacity sizing
- Bus bracing calculations
- Equipment worst-case rating
- Most conservative analysis
Typical magnitude:
- Highest fault current at any location
- 1.0 per-unit base for comparison
- Other fault types are lower
Phase-to-phase fault (2ph)
Two phases short-circuited:
- Lower current than three-phase fault
- Typically 87% of three-phase current
- Unbalanced fault
- One phase remains healthy
When to use:
- Coordination studies
- Protection device settings
- Realistic fault scenarios
- Delta-connected systems
Typical magnitude:
- About 0.87 × three-phase fault current
- Varies by system grounding and configuration
Single-phase fault (1ph)
One phase to ground:
- Common in grounded systems
- Current magnitude depends on grounding method
- Can be higher or lower than three-phase fault
- System grounding critical
Grounding effects:
Solidly grounded systems:
- Single-phase fault ≈ three-phase fault
- Low zero-sequence impedance
- High ground fault current
Resistance grounded:
- Lower ground fault current
- Intentionally limited for safety
- Common in medium voltage systems
Ungrounded systems:
- Very low ground fault current
- First fault may continue operation
- Uncommon in modern practice
When to use:
- Ground fault protection settings
- Grounding system design
- Single-phase equipment protection
- Realistic fault analysis
Phase-to-phase-earth fault (2ph-e)
Two phases to ground:
- Higher than phase-to-phase fault
- Lower than three-phase fault typically
- Unbalanced fault
- Depends on grounding impedance
When to use:
- Complete fault analysis
- Grounded systems only
- Worst-case unbalanced fault
Fault current comparison
Typical relative magnitudes (solidly grounded system):
| Fault Type | Relative Current | Use Case |
|---|---|---|
| Three-phase (3ph) | 100% | Equipment rating, worst case |
| Phase-to-phase (2ph) | 87% | Coordination, realistic faults |
| Single-phase (1ph) | 80-100% | Ground fault protection |
| Phase-to-phase-earth (2ph-e) | 90-95% | Complete analysis |
Actual values vary by system grounding and impedance.
Selecting fault type
For equipment ratings:
- Use three-phase fault
- Most conservative
- Required for breaker selection
For protection coordination:
- Calculate all fault types
- Verify protection operates correctly for all scenarios
- Minimum fault current determines sensitivity
For arc flash analysis:
- Use three-phase fault
- Highest incident energy
- Worst-case personnel protection
For comprehensive study:
- Run all fault types
- Identify limiting cases
- Verify grounding effectiveness
In EKX today, use the three-phase maximum-current result for equipment interrupting-capacity and withstand checks. Do not treat phase-to-phase, single-phase, phase-to-phase-earth, or minimum-current cases as available until the app exposes them with their own tested calculation fixtures.
System grounding influence
Solidly grounded (most common in US):
- Neutral connected directly to ground
- High ground fault current
- Single-phase fault ≈ three-phase fault
- Typical for 480V and below
Resistance grounded:
- Neutral through resistor to ground
- Limited ground fault current (5-10A typical)
- Reduces arc flash hazard
- Common in medium voltage (5-15kV)
Ungrounded:
- Neutral isolated from ground
- Very low ground fault current
- Can operate through first fault
- Rare, special applications only
Grounding method dramatically affects single-phase fault currents.
When to use each type
Routine analysis:
- Three-phase fault only
- Fastest calculation
- Covers worst case
Detailed coordination:
- Three-phase and phase-to-phase
- Verifies protection for realistic faults
- Ensures minimum fault current detected
Complete analysis:
- All fault types
- Comprehensive protection verification
- Grounding system validation
- Required for critical systems
Related topics
- Understanding short-circuit - Short-circuit analysis fundamentals
- Running analysis - How to execute short-circuit calculations
- Protection devices - Interrupting capacity based on fault currents