Fault types

Short-circuit studies use different fault types depending on the engineering question. Each type produces different fault currents and affects equipment differently.

EKX's current production calculation path supports validated three-phase maximum-current analysis only. The other fault types below are engineering background and planned validation scope, not currently enabled production workflows.

Three-phase fault (3ph)

Most severe fault:

  • All three phases short-circuited together
  • Highest fault current magnitude
  • Balanced fault (symmetrical on all phases)
  • Used for equipment rating verification

When to use:

  • Breaker interrupting capacity sizing
  • Bus bracing calculations
  • Equipment worst-case rating
  • Most conservative analysis

Typical magnitude:

  • Highest fault current at any location
  • 1.0 per-unit base for comparison
  • Other fault types are lower

Phase-to-phase fault (2ph)

Two phases short-circuited:

  • Lower current than three-phase fault
  • Typically 87% of three-phase current
  • Unbalanced fault
  • One phase remains healthy

When to use:

  • Coordination studies
  • Protection device settings
  • Realistic fault scenarios
  • Delta-connected systems

Typical magnitude:

  • About 0.87 × three-phase fault current
  • Varies by system grounding and configuration

Single-phase fault (1ph)

One phase to ground:

  • Common in grounded systems
  • Current magnitude depends on grounding method
  • Can be higher or lower than three-phase fault
  • System grounding critical

Grounding effects:

Solidly grounded systems:

  • Single-phase fault ≈ three-phase fault
  • Low zero-sequence impedance
  • High ground fault current

Resistance grounded:

  • Lower ground fault current
  • Intentionally limited for safety
  • Common in medium voltage systems

Ungrounded systems:

  • Very low ground fault current
  • First fault may continue operation
  • Uncommon in modern practice

When to use:

  • Ground fault protection settings
  • Grounding system design
  • Single-phase equipment protection
  • Realistic fault analysis

Phase-to-phase-earth fault (2ph-e)

Two phases to ground:

  • Higher than phase-to-phase fault
  • Lower than three-phase fault typically
  • Unbalanced fault
  • Depends on grounding impedance

When to use:

  • Complete fault analysis
  • Grounded systems only
  • Worst-case unbalanced fault

Fault current comparison

Typical relative magnitudes (solidly grounded system):

Fault TypeRelative CurrentUse Case
Three-phase (3ph)100%Equipment rating, worst case
Phase-to-phase (2ph)87%Coordination, realistic faults
Single-phase (1ph)80-100%Ground fault protection
Phase-to-phase-earth (2ph-e)90-95%Complete analysis

Actual values vary by system grounding and impedance.

Selecting fault type

For equipment ratings:

  • Use three-phase fault
  • Most conservative
  • Required for breaker selection

For protection coordination:

  • Calculate all fault types
  • Verify protection operates correctly for all scenarios
  • Minimum fault current determines sensitivity

For arc flash analysis:

  • Use three-phase fault
  • Highest incident energy
  • Worst-case personnel protection

For comprehensive study:

  • Run all fault types
  • Identify limiting cases
  • Verify grounding effectiveness

In EKX today, use the three-phase maximum-current result for equipment interrupting-capacity and withstand checks. Do not treat phase-to-phase, single-phase, phase-to-phase-earth, or minimum-current cases as available until the app exposes them with their own tested calculation fixtures.

System grounding influence

Solidly grounded (most common in US):

  • Neutral connected directly to ground
  • High ground fault current
  • Single-phase fault ≈ three-phase fault
  • Typical for 480V and below

Resistance grounded:

  • Neutral through resistor to ground
  • Limited ground fault current (5-10A typical)
  • Reduces arc flash hazard
  • Common in medium voltage (5-15kV)

Ungrounded:

  • Neutral isolated from ground
  • Very low ground fault current
  • Can operate through first fault
  • Rare, special applications only

Grounding method dramatically affects single-phase fault currents.

When to use each type

Routine analysis:

  • Three-phase fault only
  • Fastest calculation
  • Covers worst case

Detailed coordination:

  • Three-phase and phase-to-phase
  • Verifies protection for realistic faults
  • Ensures minimum fault current detected

Complete analysis:

  • All fault types
  • Comprehensive protection verification
  • Grounding system validation
  • Required for critical systems