Transformers

Transformers change voltage levels between different parts of your electrical system. They step voltage up for transmission efficiency or step down for distribution and utilization.

Transformer types

Power transformers:

  • Large units for utility substations
  • Ratings: 5 MVA to 500 MVA
  • Voltages: 115kV to 13.8kV, or similar ranges
  • Oil-filled with external cooling

Distribution transformers:

  • Medium-duty for building distribution
  • Ratings: 75 kVA to 5 MVA
  • Voltages: 13.8kV to 480V typical
  • Liquid or dry type

Dry-type transformers:

  • Indoor building installation
  • Ratings: 15 kVA to 2500 kVA
  • Voltages: 480V to 208V, or 600V to 480V
  • Air-cooled, no oil

Creating a transformer

  1. Drag Transformer from the component toolbar.
  2. Drop on canvas.
  3. Connect primary side (top handle) to upstream bus.
  4. Connect secondary side (bottom handle) to downstream bus.
  5. Configure ratings in edit panel.

Rated kVA

Transformer capacity in kilovolt-amperes (kVA):

Common ratings:

  • Small: 15, 30, 45, 75, 112.5, 150 kVA
  • Medium: 225, 300, 500, 750, 1000, 1500, 2000, 2500 kVA
  • Large: 3000, 5000, 7500, 10000 MVA and up

Select kVA based on total connected load plus growth margin (typically 125-150% of calculated load).

Primary and secondary voltages

Primary voltage - Input (high voltage side):

  • Where power enters the transformer
  • Examples: 13.8kV, 4.16kV, 480V

Secondary voltage - Output (low voltage side):

  • Where power exits the transformer
  • Examples: 480V, 208V, 120V

Common voltage pairs:

PrimarySecondaryApplication
13.8kV480VUtility to building distribution
4.16kV480VCampus distribution
480V208VStep-down for lighting/receptacles
208V120VSmall transformers for controls

Must match system voltages on both sides.

Impedance percentage

Transformer impedance (Z%) determines short-circuit current and voltage regulation:

Typical impedance by size:

kVA RatingTypical Z%
15-1502-3%
225-5003-4%
750-15004-5.5%
2000-25005-5.75%
5000+5.75-7%

Higher impedance = lower short-circuit current but higher voltage drop under load.

Vector groups

Vector group indicates winding connections and phase shift:

Common vector groups:

  • Dyn11: Delta primary, wye secondary, 30° phase shift - most common for distribution
  • Yy0: Wye-wye, no phase shift - utility transmission
  • Yyy0: Three-winding transformer
  • Dz0: Delta-zigzag for grounding

Most building transformers use Dyn11 configuration.

Tap changer settings

Tap changers adjust secondary voltage by changing transformer turns ratio:

No-load tap changer (NLTC):

  • Adjusted when transformer is de-energized
  • Fixed positions: typically ±2.5% or ±5%
  • Must be changed manually by technicians

On-load tap changer (OLTC):

  • Adjusts while transformer is energized
  • Automatic voltage regulation
  • Common on utility transformers
  • Rare on building transformers

Most building transformers have fixed taps set at installation.

Cooling types

Dry-type (air-cooled):

  • Forced air (fans) or natural convection
  • Indoor installation
  • No oil = no fire/environmental hazard
  • Limited to ~2500 kVA

Liquid-filled:

  • Mineral oil or silicone fluid
  • Better cooling than air
  • Outdoor or vault installation
  • All sizes available
  • Requires spill containment

Cooling designation:

  • ONAN: Oil natural, air natural (no fans/pumps)
  • ONAF: Oil natural, air forced (fans on radiators)
  • OFAF: Oil forced, air forced (pumps + fans)

Connection configurations

Single-phase transformers:

  • Two bushings (H1-H2 primary, X1-X2 secondary)
  • Used for residential and small commercial

Three-phase transformers:

  • Six bushings minimum (three-phase each side)
  • One tank with three phase windings
  • More economical than three single-phase units

Configure phase count to match your system.

Autosizing impedance

ekx can auto-populate impedance percentage based on kVA rating:

  1. Enter the rated kVA.
  2. System suggests typical Z% for that size.
  3. Accept default or override with nameplate value.

Use actual nameplate impedance when available for accurate short-circuit calculations.

Transformer annotations

After power flow analysis, transformers show:

  • Loading percentage (kVA / rated kVA × 100%)
  • Primary (HV) side current
  • Secondary (LV) side current
  • Color-coded by loading (green ≤90%, yellow >90% to 100%, red >100%)

See Power flow results.