How EKX calculates harmonics

This page describes the model behind the harmonic study: the standard EKX compares against, the source spectra, how each element changes with frequency, resonance screening, and the limits applied at the point of common coupling (PCC). Use it to reconcile EKX results with a hand calculation or another program. To set up and run the study, see Run a harmonic design study.

Standard and verdict

EKX compares results with IEEE Std 519-2022. Each result is a design prediction for the modelled case, not measured compliance. The only verdicts are "Within IEEE 519 design limits for this modeled case" and a named exceedance.

The standard states its limits as statistical tests on measurements: daily 99th percentile and weekly 99th and 95th percentile values, at 1.0 to 2.0 times the table values. A steady-state design calculation has no statistics, so EKX compares it with 1.0 times the tables, the strictest of those tests. Comparisons use unrounded values, and a value equal to its limit is an exceedance, because the standard requires each value to be less than its limit. Rounding is for display only.

EKX compares limits only at a designated PCC, never at an internal bus or a single piece of equipment. Distortion at internal buses is shown as a diagnostic with no verdict.

How the network is solved

The study solves a balanced three-phase network once at the fundamental and once at each integer order from 2 to 50. Each order is a linear solve with every element at its impedance for that frequency. The steps are:

  1. Solve the fundamental. Ordinary loads keep their load characteristic (constant power, current or impedance), and motors and drives are constant power. The utility's source impedance is included, unlike in power flow, which holds the utility bus at its operating voltage. If the solved load powers do not match the requested load models, that island's results are unavailable.
  2. Replace each harmonic source with a current source. Its fundamental current is the current solved in step 1, and each order is that current times the spectrum percentage.
  3. Replace each ordinary load with its damping impedance (see the element table below).
  4. Solve each order from 2 to 50 and record bus voltages and branch currents.

Each connected island is solved on its own, so a problem in one island makes only that island's results unavailable. An in-service generator makes its island unavailable, with a message to take the generator out of service for a utility-fed study.

Contributions of the same order add as complex phasors on one voltage base. Different orders combine by root-sum-square. Percentages are never added.

Source spectra

Variable frequency drives and UPS loads are harmonic sources. Each carries a complete spectrum for orders 2 to 50 in percent of its own solved fundamental current. A new drive starts on the six-pulse DC choke profile and a new UPS on the six-pulse thyristor profile. You can choose another profile, enter manufacturer data or import your own values in the equipment's Study tab. Each installed profile records its source publication and stated conditions, and the study report lists them.

Profile5th7th11th13thLast published order
Six-pulse, no choke80%58%18%10%25th
Six-pulse, DC choke38%20%10%8%19th
Six-pulse, 3% line reactor40%15%5%4%25th
Six-pulse, 5% line reactor32%9%4%3%25th
Six-pulse, passive harmonic filter2.5%2.5%2%2%25th
12-pulse3.7%1.2%6.9%3.2%25th
18-pulse0.6%0.8%0.5%0.4%25th
Active front end2.6%3.4%3%0.1%25th
UPS — conventional six-pulse thyristor rectifier (theoretical)20%14.3%9.1%7.7%25th

Above the last published order, the characteristic orders 6k ± 1 continue as the last published value times its order divided by h:

I_h = I_last x h_last / h      (h = 6k +/- 1, h > h_last)

For example, the DC choke profile gives 4.1% at the 19th, so its 23rd is 4.1 x 19 / 23 = 3.387%. Even and triplen orders are zero in every typical profile, as they are for a balanced six-pulse front end.

A drive that feeds a motor takes its fundamental input current from the motor and output cable it supplies. That output network is then removed from the harmonic solve, so the motor adds no damping and its emission is counted once. A Physical input reactor on a drive is a series impedance at the drive input, from its percent R and X on its own kVA and kV. The reactor does not reduce the emission percentages. To model a drive whose reactor lowers its emissions, choose a reactor-equipped profile.

Published profiles give magnitudes only. When an angle is entered, the angle of order h is the spectrum angle plus h times the source's fundamental angle. For the PCC comparison, EKX adds every contribution with an unknown angle in phase with the coherent sum of the known-angle contributions, separately for each order and each PCC. This is a worst-case bound and assumes no cancellation between drives. The diagnostic spectra at internal buses use 0° for unknown angles.

The supply has no background distortion unless you enter a background voltage spectrum in Diagram Settings > Harmonics. EKX applies that one spectrum at every utility.

Frequency scaling of each element

In this table, h is the harmonic order. Reactance at order h is h times the fundamental reactance, and capacitive susceptance is h times its fundamental value.

ElementFundamental modelChange with frequency
UtilitySource impedance from its fault level and X/R, or its per-unit Z1R constant, X x h
CableCatalogue R and X for its raceway, divided by parallel runs; capacitance times runs, or zero when the catalogue gives noneR constant, X x h, susceptance x h
Transformer%R and %X as in power flow; no-load loss as a parallel resistance; no magnetizing reactanceR constant, X x h
Capacitor bankEnergized fraction of rated kvar; loss as a parallel resistanceSusceptance x h, loss resistance constant
Shunt reactorRated kvar at rated voltage and frequency, entered resistance in seriesR constant, X x h
Direct-connected motorLocked-rotor impedance, R and X in seriesR constant, X x h
Static loadR = V^2 / P in parallel with X = V^2 / QR constant, X x h
Drive-fed motorRemoved from the harmonic solve-

Cable resistance stays at its catalogue temperature and frequency, and skin effect is not modelled. Cable reactance is first converted from the catalogue's reference frequency to the project frequency at constant inductance. NEC Chapter 9 Table 9 values are taken as 60 Hz. Other catalogue data with no stated frequency is taken as the project frequency. The study notes this conversion, which power flow does not make.

A direct-connected motor's impedance is set by its locked-rotor current and R/X, the same data the short-circuit study uses. A motor missing either makes its island unavailable.

|Z| = V_rated^2 / (S_motor x I_LR)     S_motor = P / PF, I_LR in per unit
X = |Z| / sqrt(1 + (R/X)^2),  R = X x (R/X)

Here P is the motor's electrical input power before demand, diversity and utilization factors, so the motor's operating load does not change its damping.

A static load uses its rated voltage and its operating P and Q in the selected scenario. A unity power factor load is the resistance alone, and a leading load gives a capacitor in place of the reactor.

Transformers support delta-wye windings at clock 1 or 11 and matching windings at clock 0. A delta-wye transformer is taken as clock 1 unless you enter its clock under Harmonic winding model on the transformer's Study tab. Its grounding counts as unknown until you enter it there, and unknown grounding gives no zero-sequence path. Triplen current needs a known grounded return path and zero-sequence impedance for every line and supply it reaches. Without them, results reached by that current are unavailable. The typical profiles carry no triplen orders, so this matters mainly for custom spectra and background distortion.

Resonance screening

The scan calculates the positive-sequence driving-point impedance at each PCC bus across a range of frequencies. Harmonic sources are switched off, the utility voltage is set to zero with its impedance kept, and every damping element stays in place. A parallel resonance appears as a peak in impedance magnitude.

The scan is on by default, from order 1.1 to 50 at 490 points; orders between integers are allowed. You can set the range from 1 to 50 and up to 1,000 points. The whole study is limited to 1,000 scan points, shared across PCC buses, and EKX records any reduction. A resonance peak is information, not an exceedance. Only calculated distortion is compared with limits. The scan runs only at PCC buses, so a project with no PCC has no scan.

Point of common coupling

IEEE 519 defines the PCC as the point on the public supply system electrically nearest the user at which other users are or could be connected. When the drawing has exactly one in-service utility and its connection point has exactly one bus, EKX uses that bus as the PCC, takes the utility as its boundary terminal, and records the PCC as inferred. In any other drawing, choose the PCC bus and its supply terminals in Diagram Settings > Harmonics. Each terminal has a direction so that the summed current is the current entering the installation. A project can have up to 16 PCCs. If a boundary terminal no longer connects to its PCC bus, only that PCC's current comparison becomes unavailable.

Limits applied

Voltage distortion is a percent of the rated line-to-neutral voltage at the PCC, from the PCC's nominal voltage:

V_rated,LN = V_nominal,LL / sqrt(3)
Individual:  V_h / V_rated,LN x 100
THD_V      = sqrt(sum of V_h^2, h = 2 to 50) / V_rated,LN x 100
PCC nominal voltageIndividual harmonicTHD
1.0 kV and below5.0%8.0%
Above 1 kV to 69 kV3.0%5.0%
Above 69 kV to 161 kV1.5%2.5%
Above 161 kV1.0%1.5%

Current distortion is a percent of IL, the maximum demand load current at the PCC:

Individual: I_h / IL x 100
TDD       = sqrt(sum of I_h^2, h = 2 to 50) / IL x 100

IL is the value you enter, with its source: measured demand, a utility bill or projected design demand. EKX never derives IL from solved current or equipment ratings, so without it the current comparison is unavailable. Isc is the documented utility fault current at the PCC if you enter one. Otherwise it is the three-phase fault current at the PCC calculated from the same network, with utilities at 1.0 pu and no contribution from motors, loads, capacitor banks, reactors or drives. Leaving out the installation's own contribution gives a lower Isc/IL and the stricter row.

The current table follows the PCC nominal voltage: Table 2 from 120 V to 69 kV, Table 3 above 69 kV to 161 kV, and Table 4 above 161 kV. Below 120 V the current comparison is unavailable. Table 2 is:

Isc/IL2 to 1011 to 1617 to 2223 to 3435 to 50TDD
Below 204.0%2.0%1.5%0.6%0.3%5.0%
20 to below 507.0%3.5%2.5%1.0%0.5%8.0%
50 to below 10010.0%4.5%4.0%1.5%0.7%12.0%
100 to below 100012.0%5.5%5.0%2.0%1.0%15.0%
1000 and above15.0%7.0%6.0%2.5%1.4%20.0%

A ratio on a row boundary uses the higher row, so exactly 20 uses the 20 to 50 row. Table 4 rows split at 25 and 50. The 2nd, 4th and 6th harmonics are limited to 50% of their column, and even orders from the 8th use the full column. EKX does not apply the Table 5 multipliers for higher-pulse converters, so the individual limits stay at the unmultiplied, stricter values.

IEEE 519 current limits do not apply when the installation's rated generation is at least 10% of its annual average load demand. If the project contains any generator, in service or not, EKX needs the annual average demand from Diagram Settings > Harmonics and a rated power for every generator. At 10% or more the current comparison is not applicable; without the demand or a generator rating it is unavailable. The voltage comparison is made in both cases.

Current THD on the solved fundamental is shown as a diagnostic and is never compared with a TDD limit.

What is out of scope

  • Unbalanced and single-phase networks, and connections or loads that are not three-phase.
  • Interharmonics and orders above 50.
  • Measurement statistics and measured compliance.
  • Table 5 multipliers, the HVDC allowance above 161 kV, and generation facilities.
  • Generators in operation, and sources with a dc offset.
  • Tuned passive filter design and active filter sizing.
  • Skin effect, capacitor switching transients, and derating of equipment for harmonic heating.
  • Transformers with a third winding or an unsupported clock number.
  • Additional utility fault cases. The study uses the utility's primary fault case.